Cable Almelec -AAAC-All Aluminium Alloy Conducto
Cable Almelec
Cable Almelec, designated as AAAC conductor (All Aluminum Alloy Conductor), comprises aluminum alloy 6201 wires stranded together. The AAAC conductors specified in this standard are part of the ASTER family. These cables find primary application in overhead lines within transmission and distribution electrical grids, where they are subjected to significant mechanical stress. Derudover, they serve as a sturdy support structure for suspending overhead electrical cables. AAAC conductors are versatile, suitable for medium to high voltage transmission lines across diverse voltage levels. Currently, they are extensively employed in power transmission across vast rivers, regions prone to heavy icing, and other unique geographical terrains.
We are a Cable Almelec manufacturer and factory, we sale low price and good quantity for Kabel Almelec.
Data Sheet Cable Almelec French Sizes
French Sizes
CODE NAME | AREA mm2 | NO. OF WIRES | DIAMETER OF WIRES mm | OVERALL DIAMETER OF CONDUCTOR mm | TENSILE STRENGTH OF WIRE hbar | RATED STRENGTH OF CONDUCTOR og N | MAXIMUM DC RESISTANCE AT 20ºC km | LINEAR WEIGHT kg/km | ELASTICITY MODULUS* hbar | COEFFICIENT OF LINEAR EXPANSION */oc |
ASTER 22 | 21.99 | 7 | 2 | 6 | 32.4 | 710 | 1.5 | 60.2 | 6200 | 23.10-6 |
ASTER 34.4 | 34.36 | 7 | 2.5 | 7.5 | 32.4 | 1105 | 0.958 | 94.1 | 6200 | 23.10-6 |
ASTER 54.6 | 54.55 | 7 | 3.15 | 9.45 | 32.4 | 1755 | 0.603 | 149 | 6200 | 23.10-6 |
ASTER 75.5 | 75.54 | 19 | 2.25 | 11.25 | 32.4 | 2430 | 0.438 | 208 | 6000 | 23.10-6 |
ASTER 117 | 116.98 | 19 | 2.8 | 14 | 32.4 | 3765 | 0.283 | 322 | 6000 | 23.10-6 |
ASTER 148 | 148.01 | 19 | 3.15 | 15.75 | 32.4 | 4765 | 0.224 | 407 | 6000 | 23.10-6 |
ASTER 181.6 | 181.62 | 37 | 2.5 | 17.5 | 32.4 | 5845 | 0.183 | 500 | 5700 | 23.10-6 |
ASTER 228 | 227.83 | 37 | 2.8 | 19.6 | 32.4 | 7340 | 0.146 | 627 | 5700 | 23.10-6 |
ASTER 288 | 288.34 | 37 | 3.15 | 22.05 | 32.4 | 9280 | 0.115 | 794 | 5700 | 23.10-6 |
ASTER 366 | 366.22 | 37 | 3.55 | 24.85 | 32.4 | 11785 | 0.0905 | 1009 | 5700 | 23.10-6 |
ASTER 570 | 570.22 | 61 | 3.45 | 31.05 | 32.4 | 18360 | 0.0583 | 1574 | 5400 | 23.10-6 |
ASTER 851 | 850.66 | 91 | 3.45 | 37.95 | 32.4 | 27390 | 0.0391 | 2354 | 5250 | 23.10-6 |
ASTER 1144 | 1143.51 | 91 | 4 | 44 | 31.9 | 36260 | 0.0292 | 3164 | 5250 | 23.10-6 |
ASTER 1600 | 1595.93 | 127 | 4 | 52 | 31.9 | 50640 | 0.0206 | 4425 | 5050 | 23.10-6 |
Data Sheet Cable Almelec British Sizes
British Sizes
CODE | NOMINAL AREA | EQUIVALENT Cu AREA | STRANDING AND WIRE | NOMINAL OVERALL DIAMETER | TOTAL AREA | WEIGHT | |||||
mm2 | mm2 | inch2 | mm | tomme | mm2 | inch2 | mm2 | inch2 | mm2 | lb/M ftt | |
– | – | 6.45 | 0.01 | 7/1.47 | 7/0.0574 | 4.41 | 0.174 | 11.7 | 0.01812 | 32.2 | 21.7 |
BOX | – | 9.68 | 0.015 | 7/1.85 | 7/0.0727 | 5.55 | 0.219 | 18.8 | 0.02908 | 51.7 | 34.7 |
ACACIA | – | 12.9 | 0.02 | 7/2.08 | 7/0.0822 | 6.24 | 0.246 | 23.9 | 0.03711 | 66.1 | 44.4 |
ALMOND | 25 | 16.1 | 0.025 | 7/2.34 | 7/0.0921 | 7.02 | 0.276 | 30.1 | 0.04666 | 82.9 | 55.7 |
CEDA | 30 | 19.4 | 0.03 | 7/2.54 | 7/1000 | 7.62 | 0.3 | 35.5 | 0.05498 | 97.8 | 65.7 |
– | 40 | 22.6 | 0.035 | 7/2.77 | 7/1091 | 8.31 | 0.327 | 42.2 | 0.06543 | 116.4 | 78.2 |
FIR | 50 | 25.8 | 0.04 | 7/2.95 | 70161 | 8.85 | 0.348 | 47.8 | 0.07415 | 131.8 | 88.6 |
HAZEL | 100 | 32.3 | 0.05 | 7/3.30 | 7/0.1299 | 9.9 | 0.39 | 59.9 | 0.0928 | 165 | 110.9 |
PINE | – | 38.7 | 0.06 | 7/3.61 | 70422 | 10.83 | 0.426 | 71.7 | 0.1111 | 197.7 | 132.9 |
– | – | 45.2 | 0.07 | 7/3.91 | 7/1539 | 11.73 | 0.462 | 84.1 | 0.1303 | 231.6 | 155.6 |
WILLOW | 150 | 48.4 | 0.075 | 7/4.04 | 7/1591 | 12.12 | 0.477 | 89.8 | 0.1392 | 247.5 | 166.3 |
– | 175 | 51.6 | 0.08 | 7/4.19 | 7/1650 | 12.57 | 0.495 | 96.5 | 0.149 | 266.2 | 178.9 |
– | 300 | 58.1 | 0.09 | 7/4.45 | 7/0.1751 | 13.35 | 0.526 | 108.8 | 0.1686 | 299.8 | 201.5 |
OAK | – | 64.5 | 0.1 | 7/4.65 | 70831 | 13.95 | 0.549 | 118.9 | 0.1843 | 327.8 | 220.3 |
– | – | 64.5 | 0.1 | 19/2.82 | 190111 | 14.1 | 0.555 | 118.8 | 0.1841 | 327.6 | 220.2 |
MULBERRY | – | 80.6 | 0.125 | 19/3.18 | 19/1253 | 15.9 | 0.626 | 151.1 | 0.2342 | 416.7 | 280 |
ASH | – | 96.8 | 0.15 | 19/3.48 | 19/1370 | 17.4 | 0.685 | 180.7 | 0.2801 | 498.1 | 334.8 |
ELM | – | 113 | 0.175 | 19/3.76 | 19/1481 | 18.8 | 0.74 | 211 | 0.3271 | 582.1 | 391.2 |
POPLAR | – | 129 | 0.2 | 37/2.87 | 37/1129 | 20.09 | 0.791 | 239 | 0.3705 | 658.8 | 442.7 |
– | – | 145 | 0.225 | 37/3.05 | 37/1202 | 21.35 | 0.841 | 270.8 | 0.4197 | 746.7 | 501.8 |
SYCAMORE | – | 161 | 0.25 | 37/3.23 | 37/0.1271 | 22.61 | 0.89 | 303 | 0.4697 | 834.9 | 561.1 |
UPAS | – | 194 | 0.3 | 37/3.53 | 37/1390 | 24.71 | 0.973 | 362.1 | 0.5613 | 998.6 | 671.1 |
– | – | 226 | 0.35 | 37/3.81 | 370500 | 26.47 | 1.05 | 421.8 | 0.6538 | 1163 | 781.5 |
YEW | – | 258 | 0.4 | 37/4.06 | 370600 | 28.42 | 1.119 | 479.9 | 0.7439 | 1323 | 889.2 |
Cable Almelec 148 mm2
TECHNICAL DATA SHEET | |||
Câble Almélec 148 mm² ASTER | |||
NO | DESCRIPTION | UNIT | DATA |
1 | Type/ code name | — | Almelec 148 |
2 | Materiale | — | Aluminium Alloy |
3 | Standards | — | IEC 61089,NFC 34 125,NF EN 50182 |
4 | Cross Section Area | mm2 | 148 |
Cable Almelec 34.4 mm2
TECHNICAL DATA SHEET | |||
Câble Almélec 34.4 mm² ASTER | |||
NO | DESCRIPTION | UNIT | DATA |
1 | Type/ code name | — | Almelec 34.4 |
2 | Materiale | — | Aluminium Alloy |
3 | Standards | — | IEC 61089,NFC 34 125,NF EN 50182 |
4 | Cross Section Area | mm2 | 34.4 |
Cable Almelec 93 mm2
TECHNICAL DATA SHEET | |||
Câble Almélec 93 mm² ASTER | |||
NO | DESCRIPTION | UNIT | DATA |
1 | Type/ code name | — | Almelec 93 |
2 | Materiale | — | Aluminium Alloy |
3 | Standards | — | IEC 61089,NFC 34 125,NF EN 50182 |
4 | Cross Section Area | mm2 | 93 |
Cable Almelec 54.6 mm2
TECHNICAL DATA SHEET | |||
Câble Almélec 54.6 mm² ASTER | |||
NO | DESCRIPTION | UNIT | DATA |
1 | Type/ code name | — | Almelec 54.6 |
2 | Materiale | — | Aluminium Alloy |
3 | Standards | — | IEC 61089,NFC 34 125,NF EN 50182 |
4 | Cross Section Area | mm2 | 54.6 |
Cable Almelec 570 mm2
TECHNICAL DATA SHEET | |||
Câble Almélec 570 mm² ASTER | |||
NO | DESCRIPTION | UNIT | DATA |
1 | Type/ code name | — | Almelec 570 |
2 | Materiale | — | Aluminium Alloy |
3 | Standards | — | IEC 61089,NFC 34 125,NF EN 50182 |
4 | Cross Section Area | mm2 | 570 |