NA2XSA2Y-S Cable

NA2XSA2Y-S

NA2XSA2Y-S Cable

What is NA2XSA2Y-S Cable?

NA2XSA2Y-S

Conductor: Stranded compact circular aluminum conductor according to IEC60228 class 2

Driver screen: Extruded Semiconductor Compound

Isolation: XLPE (cross-linked polyethylene) classified to 90 °C

insulating screen: Extruded Semiconductor Compound

Metal screen: Aluminum tape.

Deck: Linear low density polyethylene LLDPE-UV.

Courier driver: Braided Galvanized Steel Cable.

Messenger Isolation: Linear low density polyethylene LLDPE-UV.

Technical parameters of NA2XSA2Y-S 6/10kV cable

ConductorApproximate outside diameter mm Courier driver (EHS)Approximate weight kg/km
Number of cores x nominal cross section
N.° × mm²

Number of cables (min)

Nominal conductor diameter
mm
Braid No. × mmMessenger conductor diameter mmMinimum breaking load kN
3X1X2565.942.47×2.647.9249.821562
3X1X3566.944.67×2.647.9249.821714
3X1X5068.147.27×2.647.9249.821908
3X1X70129.850.87×2.647.9249.822200
3X1X951511.454.37×3.6811.0492.822855
3X1X1201512.857.37×3.6811.0492.823153
3X1X1501514.461.27×3.6811.0492.823523
3X1X185301664.67×3.6811.0492.823933
3X1X2403018.470.27×3.6811.0492.824611

Technical parameters of NA2XSA2Y-S 8.7/15kV cable

ConductorApproximate outside diameter mm Courier driver (EHS)Approximate weight kg/km
Number of cores x nominal cross section
N.° × mm²

Number of cables (min)

Nominal conductor diameter
mm
Braid No. × mmMessenger conductor diameter mmMinimum breaking load kN
3X1X2565.947.27×2.647.9249.821799
3X1X3566.949.37×2.647.9249.821962
3X1X5068.151.97×2.647.9249.822168
3X1X70129.855.67×2.647.9249.822477
3X1X951511.459.07×3.6811.0492.823149
3X1X1201512.862.57×3.6811.0492.823490
3X1X1501514.465.97×3.6811.0492.823851
3X1X185301669.87×3.6811.0492.824308
3X1X2403018.475.47×3.6811.0492.825016

Technical parameters of NA2XSA2Y-S 12/20kV cable

ConductorApproximate outside diameter mm Courier driver (EHS)Approximate weight kg/km
Number of cores x nominal cross section
N.° × mm²
Number of cables (min)

Nominal conductor diameter
mm
Braid No. × mmMessenger conductor diameter mmMinimum breaking load kN
3X1X3566.954.17×3.00964.362337
3X1X5068.156.77×3.00964.362555
3X1X70129.860.37×3.00964.362883
3X1X951511.464.27×3.00964.363277
3X1X1201512.867.67×3.00964.363636
3X1X1501514.471.17×3.00964.364015
3X1X1853016757×3.00964.364493
3X1X2403018.480.17×3.00964.365196

Technical parameters of NA2XSA2Y-S 18/30kV cable

ConductorApproximate outside diameter mm Courier driver (EHS)Approximate weight kg/km
Number of cores x nominal cross section
N.° × mm²

Number of cables (min)

Nominal conductor diameter
mm
Braid No. × mmMessenger conductor diameter mmMinimum breaking load kN
3X1X3566.954.17×3.00964.362337
3X1X5068.167.97×2.647.9249.823208
3X1X70129.871.57×2.647.9249.823577
3X1X951511.475.47×3.6811.0492.824339
3X1X1201512.878.47×3.6811.0492.824703
3X1X1501514.482.319×2.8614.29149.95571
3X1X185301686.219×2.8614.29149.96093
3X1X2403018.491.319×2.8614.29149.96854

Technical data of NA2XSA2Y-S Cable

The product is suitable for power transmission and distribution lines with a rated power frequency voltage of 6 kV a 30 kV.

Nominal voltages U0/U(One): 6/10(12) kV, 8,7/15(17,5) kV, 12/20(24) kV, 18/30(36) kV;
Use: The above nominal voltages are equivalent to 6,35/11(12) kV, 8,7/15(17,5) kV, 12,7/22(24) kV, 19/33(36) kV;

U0: rated power frequency voltage between conductor and earth or armor, the metal sheath or screen for which the cable is suitable.

U: rated power frequency voltage between phase conductors for which the cable is suitable.

One :Maximum value of the highest system voltage between phase conductors for which the cable is suitable.

Ambient temperature for installation: ≥0℃

Maximum conductor temperature in normal operation: ≤90℃

Maximum operating temperature of the conductor when the cable is shorted (maximum duration of 5 s): 250℃

Minimum allowed curvature radius: 15 x outer diameter

Use: outer diameter = outer diameter of the cable

NA2XSA2Y-S Cable Durability

NA2XSA2Y-S cable has been designed to offer resistance in various operating conditions, including extreme temperature, presence of water, UV radiation exposure and abrasion resistance. Its robust construction and high-quality material used in its manufacturing guarantee a long life cycle and low failure rate..

Temperature Resistance: The NA2XSA2Y-S cable can operate in temperatures from -40 °C up to 90 °C, covering a wide range of environmental conditions.
Impermeability: The cable is designed to prevent water entry longitudinally, avoiding short circuit problems and damage to critical installations.
UV protection: Protective cover in black meets UV protection standards, ensuring that the cable can be permanently used in outdoor applications.

NA2XSA2Y-S Cable Applications

Electrical networks: to transmit electrical energy from power generation plants to substations and then to distribution networks, NA2XSA2Y-S cable could be used in underground or overhead installations.

Industrial applications: in factories, mines and other industrial environments, the cable could be used to connect electrical equipment, engines, transformers and other components within the facility's power distribution system.

Infrastructure projects: for large-scale infrastructure projects, like airports, tunnels, bridges and road networks, NA2XSA2Y-S cable can be specified for durability, impermeability and resistance to environmental factors.

Renewable energy systems: in wind farms, solar parks and other renewable energy generation facilities, the cable could be used to connect turbines, panels and other power generating units to the main electrical grid.

Utility networks: public service companies, including water, gas and electricity, They often use specialized cables in their networks. NA2XSA2Y-S cable could be tailored to specific requirements within these networks, such as greater fire resistance, low smoke emission or resistance to chemicals and other environmental hazards.

Marine and offshore facilities: due to its potential waterproofing and resistance to salt water corrosion, The cable could be suitable for use in marine and offshore environments, such as connecting offshore wind turbines, submarine cables or submarine power distribution systems.

It is important to note that the exact specifications and capabilities of the cable NA2XSA2Y-S will depend on the manufacturer and specific application requirements. Always consult the manufacturer's technical documentation and specifications before selecting and using the cable.

NA2XSA2Y-S Cable Fabricante, sales, precio

Dosense Cable, cable specialists NA2XSA2Y-S, offers high quality cabling solutions at incredibly low prices. Our manufacturing experience guarantees long-lasting and reliable cables, perfect for electrical and infrastructure projects. Contact us and find out why our cables are the best investment for your project.

    Request a free quote, we will answer you in 24 hours.

    Your e-mail*:

    Your name*:

    Your country:

    Your telephone*:

    Your message*:

    Animated Social Media Icons by Acurax Responsive Web Designing Company