2/0-2/0-1 Converse Aluminum XLPE URD Triplex Direct Burial Cable

Triplex URD Cable

Contact Us

2/0-2/0-1 Converse Aluminum XLPE URD Triplex Direct Burial Cable

What is 2/0-2/0-1 Converse Aluminum XLPE URD Triplex Direct Burial Cable?

2/0-2/0-1 Converse Aluminum XLPE URD triplex Direct Burial Cable It is intended for use in secondary distribution circuits, being suitable for installation in conduits or for direct burial applications. Maximum operating temperature should not exceed 90°C in wet and dry locations. The nominal voltage is 600 volts. As an option, This cable can be delivered pre-installed in conduit.

Also know as: 2/0-2/0-1 converse XLPE aluminum urd cable, 2/0-2/0-1 converse XLPE aluminum urd direct burial cable, 2/0-2/0-1 converse XLPE aluminum three conductor cable, 2 /0-2/0-1 converse XLPE aluminum triplex cable, 2/0-2/0-1 converse XLPE aluminum triplex cable, 2/0-2/0-1 converse XLPE triplex aluminum underground cable, 2/0-2/0-1 power cord 3 converse XLPE aluminum conductors, aluminum triplex aluminum converse 2/0-2/0-1 XLPE, converse aluminum underground triplex 2/0-2/0-1 XLPE, converse aluminum triplex 2/0-2/0-1 XLPE underground cable, 2/0-2/0-1 XLPE underground convert aluminum triplex cable, 2/0-2/0-1 converse XLPE aluminum direct burial triplex, 2/0-2/0-1 converse XLPE aluminum triplex conductor, 2/0 -Cable eléctrico de enterramiento directo de aluminio converse 2/0-1 XLPE, cable de alimentación de entierro directo de aluminio converse 2/0-2/0-1 XLPE, cable de entierro directo de aluminio converse 2/0-2/0-1 XLPE.

Standard of 2/0-2/0-1 Converse Aluminum XLPE URD Triplex Direct Burial Cable

ICEA S-105-6922 Standard for Specification of Control Cables, thermocouple extension and instrumentation.
ASTM B-230 Standard Specification for 1350-H19 Aluminum Wire for Electrical Purposes
ASTM B-609 Standard Specification for Aluminum Round Wire 1350, annealed and intermediate tempering, for electrical purposes
ASTM B-231 Standard Specification for Aluminum Conductor 1350 concentric braids
ASTM B-901 Standard Specification for Compressed Round Stranded Aluminum Conductor, supported in coated steel (ACSR/TW)
Accepted by Russia Accepted by the Rural Public Utilities Service
Federal Specification J-C-30 B Federal Specification for Cables, energy, electricity and control, type W

Technical data 2/0-2/0-1 Converse Aluminum XLPE URD Triplex Direct Burial Cable

Phase conductor size: 2/0
Phase conductor insulation thickness: 0,080 inches
Neutral conductor size: 1 AWG
Espesor del aislamiento del conductor neutro: 0,080 inches
External diameter: 1,17 inches
Resistencia CA a 75 °C: 0,159
Resistencia CA a 90 °C: 0,167
Resistencia inductiva a 60 Hz: 0,0280
Allowable ampacity: direct burial: 233 amps 90 °C
Allowable ampacity in duct: 180 amperes to 90 °C

URD Cable Applications

2/0-2/0-1 Converse Cable URD tiene una capacidad de corriente nominal que depende de varios factores, including ambient temperature, installation and specific conditions of use. However, 2/0-2/0-1 suelen tener una capacidad de corriente bastante alta debido a su grosor y diseño.

The current capacity of a cable is determined taking into account the maximum allowable temperature of the conductor, heat dissipation capacity, and other safety factors. In general, This capacity is specified in tables provided by cable manufacturers or electrical engineering regulations..

    Request a free quote, we will answer you in 24 hours.

    Your e-mail*:

    Your name*:

    Your country:

    Your telephone*:

    Your message*:

    Social Network Widget by Acurax Small Business Website Designers