250-250-3/0 Pratt Aluminum XLPE URD Triplex Cable De Entierro Directo
What is 250-250-3/0 Pratt Aluminum XLPE URD Triplex Cable De Entierro Directo?
250-250-3/0 Pratt Aluminum XLPE URD Triplex Cable De Entierro Directo It is intended for use in secondary distribution circuits, being suitable for installation in conduits or for direct burial applications. Maximum operating temperature should not exceed 90°C in wet and dry locations. The nominal voltage is 600 volts. As an option, This cable can be delivered pre-installed in conduit.
Also know as: cable urd de aluminio 250-250-3/0 pratt, cable de enterramiento directo pratt urd 250-250-3/0, cable de tres conductores pratt 250-250-3/0, cable triple pratt 250-250-3/0 cable plex, cable triplex pratt 250-250-3/0, cable subterráneo de aluminio triplex pratt 250-250-3/0, power cord 3 conductores pratt 250-250-3/0, triplex de aluminio 250-250-3/0 pratt , 250-250-3/0 pratt triplex subterráneo, 250-250-3/0 pratt triplex cable subterráneo, 250-250-3/0 pratt triplex cable subterráneo, 250-250-3/0 pratt triplex enterrado directo, 250- Conductor triplex pratt 250-3/0, cable eléctrico de entierro directo pratt 250-250-3/0, cable de alimentación de entierro directo pratt 250-250-3/0, cable de entierro directo de aluminio pratt 250-250-3/0.
Standard of 250-250-3/0 Pratt Aluminum XLPE URD Triplex Cable De Entierro Directo
ICEA S-105-6922 Standard for Specification of Control Cables, thermocouple extension and instrumentation.
ASTM B-230 Standard Specification for 1350-H19 Aluminum Wire for Electrical Purposes
ASTM B-609 Standard Specification for Aluminum Round Wire 1350, annealed and intermediate tempering, for electrical purposes
ASTM B-231 Standard Specification for Aluminum Conductor 1350 concentric braids
ASTM B-901 Standard Specification for Compressed Round Stranded Aluminum Conductor, supported in coated steel (ACSR/TW)
Accepted by Russia Accepted by the Rural Public Utilities Service
Federal Specification J-C-30 B Federal Specification for Cables, energy, electricity and control, type W
Technical data 250-250-3/0 Pratt Aluminum XLPE URD Triplex Cable De Entierro Directo
Phase conductor size: 250 MCM
Hilo conductor: 37
Neutral conductor size: 3/0
Hilo conductor: 19
Insulation thickness: 0,080 inches
External diameter: 1.530 inches
Allowable ampacity: direct burial: 329 amperes to 90 °C
Allowable ampacity in duct: 265 amperes to 90 °C
Weight: 0,855 pounds per foot
URD Cable Applications
250-250-3/0AWG Cable URD tiene una capacidad de corriente nominal que depende de varios factores, including ambient temperature, installation and specific conditions of use. However, los 250-250-3/0AWG tener una capacidad de corriente bastante alta debido a su grosor y diseño.
The current capacity of a cable is determined taking into account the maximum allowable temperature of the conductor, heat dissipation capacity, and other safety factors. In general, This capacity is specified in tables provided by cable manufacturers or electrical engineering regulations..