350-350-4/0 Wesleyan Aluminum XLPE URD Triplex Direct Burial Cable
What is 350-350-4/0 Wesleyan Aluminio XLPE URD Triplex Cable De Entierro Directo?
350-350-4/0 Wesleyan cable de entierro directo URD de triplex aluminio It is intended for use in secondary distribution circuits, being suitable for installation in conduits or for direct burial applications. Maximum operating temperature should not exceed 90°C in wet and dry locations. The nominal voltage is 600 volts. As an option, This cable can be delivered pre-installed in conduit.
Also know as: cable urd de aluminio wesleyano 350-350-4/0 XLPE, cable de enterramiento directo urd wesleyano 350-350-4/0 XLPE, cable triconductor wesleyano 350-350-4/0 XLPE, trivan wesleyano 350-350-4/0 alambre plex XLPE, cable triplex wesleyano 350-350-4/0 XLPE, cable subterráneo de aluminio triplex wesleyano 350-350-4/0 XLPE, cable de alimentación wesleyano de 3 drivers 350-350-4/0 XLPE, triplex de aluminio wesleyano 350-350-4/0 XLPE , 350-350-4/0 triplex subterráneo wesleyano XLPE, 350-350-4/0 cable subterráneo triplex wesleyano XLPE, 350-350-4/0 cable triplex wesleyano subterráneo XLPE, 350-350-4/0 triplex wesleyano de entierro directo XLPE, 350- Conductor triplex wesleyano 350-4/0 XLPE, cable eléctrico wesleyano de entierro directo 350-350-4/0 XLPE, cable de alimentación wesleyano de entierro directo 350-350-4/0 XLPE, cable de alimentación wesleyano de entierro directo 350-350-4/0 XLPE.
Standard of 350-350-4/0 Wesleyan Aluminum XLPE URD Triplex Direct Burial Cable
ICEA S-105-6922 Standard for Specification of Control Cables, thermocouple extension and instrumentation.
ASTM B-230 Standard Specification for 1350-H19 Aluminum Wire for Electrical Purposes
ASTM B-609 Standard Specification for Aluminum Round Wire 1350, annealed and intermediate tempering, for electrical purposes
ASTM B-231 Standard Specification for Aluminum Conductor 1350 concentric braids
ASTM B-901 Standard Specification for Compressed Round Stranded Aluminum Conductor, supported in coated steel (ACSR/TW)
Accepted by Russia Accepted by the Rural Public Utilities Service
Federal Specification J-C-30 B Federal Specification for Cables, energy, electricity and control, type W
Technical data 350-350-4/0 Wesleyan Aluminum XLPE URD Triplex Direct Burial Cable
Phase conductor size: 350 MCM
Phase conductor insulation thickness: 0,095 inches.
Neutral conductor size: 4/0
Espesor del aislamiento del conductor neutro: 0,080 inches
External diameter: 1,72 inches
Allowable ampacity: direct burial: 395 amps 90 °C
Allowable ampacity in duct: 320 amperes to 90 °C
URD Cable Applications
350-350-4/0 Cable URD tiene una capacidad de corriente nominal que depende de varios factores, including ambient temperature, installation and specific conditions of use. However, los 350-350-4/0 Cable URD suelen tener una capacidad de corriente bastante alta debido a su grosor y diseño.
The current capacity of a cable is determined taking into account the maximum allowable temperature of the conductor, heat dissipation capacity, and other safety factors. In general, This capacity is specified in tables provided by cable manufacturers or electrical engineering regulations..