750-750-500 Fairfield Aluminum XLPE URD Triplex Direct Burial Cable
What is 750-750-500 Fairfield Aluminum XLPE URD Triplex Direct Burial Cable?
750-750-500 Fairfield Aluminum XLPE URD Triplex Direct Burial Cable It is intended for use in secondary distribution circuits, being suitable for installation in conduits or for direct burial applications. Maximum operating temperature should not exceed 90°C in wet and dry locations. The nominal voltage is 600 volts. As an option, This cable can be delivered pre-installed in conduit.
Also know as: Fairfield aluminum urd cable 750-750-500 such as XLPE, Fairfield direct burial urd cable 750-750-500 such as XLPE, cable triplex Fairfield de 750-750-500 such as XLPE, cable triplex Fairfield de 750-750-500 such as XLPE, 750 -Cable Fairfield Triplex de 750-500 such as XLPE, Fairfield Triplex Aluminum Underground Cable 750-750-500 such as XLPE, power cord 3 Fairfield drivers 750-750-500 such as XLPE, Fairfield Aluminum Triplex 750-750-500 such as XLPE, Fairfield de 750-750-500 mcm triplex underground XLPE, fairfield triplex underground cable 750-750-500 such as XLPE, cable triplex triplex de 750-750-500 mcm underground XLPE, fairfield direct burial triplex 750-750-500 such as XLPE, conductor triplex fairfield de 750-750-500 such as XLPE, 750-750- Fairfield Direct Burial Electrical Cable 500 such as XLPE, Fairfield direct burial power cable 750-750-500 such as XLPE, Fairfield Aluminum Direct Burial Cable 750-750-500 such as XLPE.
Standard of 750-750-500 Fairfield Aluminum XLPE URD Triplex Direct Burial Cable
ICEA S-105-6922 Standard for Specification of Control Cables, thermocouple extension and instrumentation.
ASTM B-230 Standard Specification for 1350-H19 Aluminum Wire for Electrical Purposes
ASTM B-609 Standard Specification for Aluminum Round Wire 1350, annealed and intermediate tempering, for electrical purposes
ASTM B-231 Standard Specification for Aluminum Conductor 1350 concentric braids
ASTM B-901 Standard Specification for Compressed Round Stranded Aluminum Conductor, supported in coated steel (ACSR/TW)
Accepted by Russia Accepted by the Rural Public Utilities Service
Federal Specification J-C-30 B Federal Specification for Cables, energy, electricity and control, type W
Technical data 750-750-500 Fairfield Aluminum XLPE URD Triplex Direct Burial Cable
Phase conductor size: 750 MCM
Phase conductor insulation thickness: 0,110 inches.
Neutral conductor size: 500 MCM
Neutral conductor insulation thickness: 0,095 inches.
Allowable ampacity: direct burial: 615 amperes to 90 °C
Allowable ampacity in duct: 525 amperes to 90 °C
External diameter: 2,04 inches
URD Cable Applications
750-750-500 fairfield cable URD has a rated current capacity that depends on several factors, including ambient temperature, installation and specific conditions of use. However, los 750-750-500 fairfield have a fairly high current capacity due to its thickness and design.
The current capacity of a cable is determined taking into account the maximum allowable temperature of the conductor, heat dissipation capacity, and other safety factors. In general, This capacity is specified in tables provided by cable manufacturers or electrical engineering regulations..