XLPE/PVC Concentric Cable
Concentric Cable Construction and materials
Construction and materials concentric cables XLPE/PVC:
Conductor central: copper, aluminium alloy.
insulating layer: XLPE, PVC.
Concentric wire: copper, aluminium alloy
Funda: XLPE, PVC, etc.
The construction and material selection of concentric cables generally depends on the application environment, the voltage level and the relevant technical standards and specification requirements. It is designed to ensure reliable performance, durability and safety in a variety of electrical installations and power distribution systems.
Concentric cable standard
ASTMB8, IEC60502-1, UL44, UL1581, UL854,IEC60502-1,BS7870
ASTM Technical Data of Concentric Cables
Nominal and core cross section | Conductor | Insulation thickness | Insulation thickness | Cable outer diameter | Maximum DC resistance of the conductor (20℃) | ||
Cable gauge | Number | Diameter mm | mm | mm | mm | Oh/km | |
copper conductor (American standard) | |||||||
2X 12AWG | 7 | 0.78 | 1.14 | 1.14 | 7.74 | 5.43 | |
2X 10AWG | 7 | 0.98 | 1.14 | 1.14 | 8.72 | 3.41 | |
2X 8AWG | 7 | 1.23 | 1.14 | 1.14 | 9.74 | 2.14 | |
2X 6AWG | 7 | 1.55 | 1.14 | 1.14 | 11.04 | 1.35 | |
2X 4AWG | 7 | 1.96 | 1.14 | 1.14 | 12.68 | 0.848 | |
3X 8AWG | 7 | 1.23 | 1.14 | 1.14 | 11.3X17.3 | 2.14 | |
3X 6AWG | 7 | 1.55 | 1.14 | 1.52 | 13.2X20.2 | 1.35 | |
3X 4AWG | 7 | 1.96 | 1.14 | 1.52 | 14.7X22.9 | 0.848 | |
3X 2AWG | 7 | 2.47 | 1.14 | 1.52 | 16.6X26.3 | 0.524 | |
Aluminum alloy driver (American standard) | |||||||
2X 12AWG | 7 | 0.78 | 1.14 | 1.14 | 7.74 | 8.88 | |
2X 10AWG | 7 | 0.98 | 1.14 | 1.14 | 8.72 | 5.59 | |
2X 8AWG | 7 | 1.23 | 1.14 | 1.14 | 9.74 | 3.52 | |
2X 6AWG | 7 | 1.55 | 1.14 | 1.14 | 11.04 | 2.21 | |
2X 4AWG | 7 | 1.96 | 1.14 | 1.14 | 12.68 | 1.39 | |
3X 8AWG | 7 | 1.23 | 1.14 | 1.14 | 11.3X17.3 | 3.52 | |
3X 6AWG | 7 | 1.55 | 1.14 | 1.52 | 13.2X20.2 | 2.21 | |
3X 4AWG | 7 | 1.96 | 1.14 | 1.52 | 14.7X22.9 | 1.39 | |
3X 2AWG | 7 | 2.47 | 1.14 | 1.52 | 16.6X26.3 | 0.88 |
IEC technical data of concentric cables
Nominal and core cross section | Conductor | Insulation thickness | Concentric conductor | Cable sheath thickness | Cable outer diameter | Maximum DC resistance of the conductor (20℃) | |||
mm2 | Number | Diameter mm | mm | Number | Diameter mm | mm | mm | Oh/km | |
copper conductor (IEC standard) | |||||||||
2X10 | 7 | 1.35 | 1.55 | 20 | 0.85 | 1.4 | 11.8 | 1.83 | |
2X16 | 7 | 1.7 | 1.55 | 32 | 0.85 | 1.4 | 12.84 | 1.15 | |
2X25 | 7 | 2.14 | 1.6 | 29 | 1.13 | 1.5 | 15.02 | 0.727 | |
2X35 | 19 | 1.53 | 1.65 | 27 | 1.35 | 1.6 | 17 | 0.524 | |
Aluminum alloy driver (IEC standard) | |||||||||
2X10 | 7 | 1.35 | 1.55 | 23 | 1.13 | 1.4 | 12.41 | 3.08 | |
2X16 | 7 | 1.7 | 1.55 | 26 | 1.13 | 1.4 | 13.46 | 1.91 | |
2X25 | 7 | 2.14 | 1.6 | 29 | 1.13 | 1.5 | 15.08 | 1.2 | |
2X35 | 19 | 1.53 | 1.65 | 27 | 1.35 | 1.6 | 17.05 | 0.868 |