22kV and 35kV AAC ACSR XLPE Overhead Cable for Myanmar
22kV 35kV AAC ACSR XLPE Cable
22kV ACSR-CX, 35kV ACSR-CX
22kV AL-CX, 35kV AL-CX
22kV ACSR-X, 35kV ACSR-X
22kV AL-X, 35kV AL-X
22kV 35kV AAC ACSR XLPE Overhead Cable For Myanmar
Construction: Conducteur entièrement en aluminium, Conducteur en aluminium renforcé d'acier (ACSR), featuring stranded aluminum conductors and galvanized steel reinforcement, along with Semi-Conducting Screened Cross-Linked Polyethylene (XLPE) Insulation Power Cable.
Option: The stranded conductor layer shall be filled with water-blocking material.
Application: Suitable for overhead power transmission and distribution lines.

22kV ACSR-CX (BS EN 50397-1)
Conducteur | Épaisseur of Insulation | Environ. overall Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C. Conducteur Resistance(20℃) | |||
Gross Sectional Zone | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Acier) | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 2.5 | 17 | 330 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 2.5 | 18 | 430 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 2.5 | 20 | 560 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 2.5 | 22 | 660 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 2.5 | 24 | 760 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 2.5 | 24 | 810 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 2.5 | 26 | 930 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 2.5 | 26 | 960 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 2.5 | 29 | 1180 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 2.5 | 31 | 1410 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 2.5 | 32 | 1550 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 2.5 | 35 | 1810 | 120.481 | 0.0733 |
35kV ACSR-CX (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Environ. overall Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C. Conducteur Resistance(20℃) | |||
Gross Sectional Zone | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Acier) | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 3.9 | 19 | 400 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 3.9 | 21 | 510 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 3.9 | 23 | 650 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 3.9 | 25 | 760 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 3.9 | 26 | 860 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 3.9 | 27 | 910 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 3.9 | 29 | 1040 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 3.9 | 29 | 1070 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 3.9 | 31 | 1300 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 3.9 | 34 | 1540 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 3.9 | 35 | 1690 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 3.9 | 37 | 1960 | 120.481 | 0.0733 |
22kV AL-CX (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Apprax. Dans l'ensemble Diamètre | Approx. Overalal Poids | Min. Breaking Load | Max.D.C. Conducteur Resistance(20℃) | ||
Coss Sectional Zone | Na. and Diameter of wires | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 2.5 | 13 | 170 | 4.5 | 1.1489 |
35 | 7/2.51 | 753 | 2.5 | 15 | 200 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 2.5 | 16 | 260 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 2.5 | 17 | 330 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 25 | 19 | 410 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 2.5 | 21 | 500 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 2.5 | 23 | 600 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 25 | 24 | 720 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 25 | 27 | 900 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 2.5 | 29 | 1050 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 2.5 | 33 | 1360 | 63.42 | 0.074 |
35kV AL-CX (BS EN 50397-1)
Conducteur | Diamètre extérieur approximatif mm | Chauffeur de messagerie (EHS) | Poids approximatif kg/km | ||||
Nombre de conducteurs x section nominale N° × mm² | Nombre de câbles (min) | Diamètre nominal du conducteur mm | N° de tresse × mm | Diamètre du conducteur messager mm | Charge de rupture minimale kN | ||
3X1X35 | 6 | 6.9 | 54.1 | 7×3,00 | 9 | 64.36 | 2337 |
3X1X50 | 6 | 8.1 | 67.9 | 7×2,64 | 7.92 | 49.82 | 3208 |
3X1X70 | 12 | 9.8 | 71.5 | 7×2,64 | 7.92 | 49.82 | 3577 |
3X1X95 | 15 | 11.4 | 75.4 | 7×3,68 | 11.04 | 92.82 | 4339 |
3X1X120 | 15 | 12.8 | 78.4 | 7×3,68 | 11.04 | 92.82 | 4703 |
3X1X150 | 15 | 14.4 | 82.3 | 19×2,86 | 14.29 | 149.9 | 5571 |
3X1X185 | 30 | 16 | 86.2 | 19×2,86 | 14.29 | 149.9 | 6093 |
3X1X240 | 30 | 18.4 | 91.3 | 19×2,86 | 14.29 | 149.9 | 6854 |
22kV ACSR-X (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Environ. overall Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C. Conducteur Resistance(20℃) | |||
Gross Sectional Zone | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Acier) | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 3.5 | 17 | 340 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 3.5 | 19 | 440 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 3.5 | 21 | 570 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 3.5 | 23 | 680 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 3.5 | 24 | 780 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 3.5 | 25 | 830 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 3.5 | 26 | 950 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 3.5 | 26 | 970 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 3.5 | 29 | 1195 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 3.5 | 32 | 1430 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 3.5 | 33 | 1570 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 3.5 | 35.1 | 1830 | 120.481 | 0.0733 |
35kV ACSR-X (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Environ. overall Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C. Conducteur Resistance(20℃) | |||
Gross Sectional Zone | Na.and Diameter of wires(Al) | Na. and Diameter of wires(Acier) | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | mm | kg/km | kN | Ω/ km |
50/8 | 6/3.20 | 1/3.20 | 9.6 | 55 | 21 | 450 | 17.112 | 0.5951 |
70/11 | 6/3.80 | 1/3.80 | 11.4 | 55 | 23 | 560 | 24.13 | 0.4218 |
95/16 | 6/4.50 | 1/4.50 | 13.5 | 55 | 25 | 710 | 33.369 | 0.3007 |
120/19 | 26/2.40 | 7/1.85 | 15.15 | 55 | 27 | 820 | 41.521 | 0.244 |
150/19 | 24/2.80 | 7/1.85 | 16.75 | 55 | 28 | 930 | 46.307 | 0.2046 |
150/24 | 26/2.70 | 7/2.10 | 17.1 | 55 | 29 | 980 | 52.279 | 0.2039 |
185/24 | 24/3.15 | 7/2.10 | 18.9 | 5.5 | 30 | 1110 | 58.075 | 0.154 |
185/29 | 26/2.98 | 7/2.30 | 18.82 | 55 | 30 | 1130 | 62.055 | 0.1519 |
240/32 | 24/3.60 | 7/2.40 | 21.6 | 5.5 | 33 | 1370 | 75.05 | 0.1182 |
300/39 | 24/4.00 | 7/2.65 | 23.95 | 55 | 36 | 1630 | 90.574 | 0.0958 |
330/43 | 54/2.80 | 7/2.80 | 25.2 | 55 | 37 | 1770 | 103.784 | 0.0869 |
400/51 | 54/3.05 | 7/3.05 | 27.5 | 55 | 39 | 2050 | 120.481 | 0.0733 |
22kV AL-X (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Environ. Dans l'ensemble Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C Conducteur Resistance(20℃ | ||
Coss Sectional Zone | Na. and Diameter of wires | Outside Diameter | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 3.5 | 14 | 180 | 4.5 | 1.1489 |
35 | 7/2.51 | 7.53 | 3.5 | 15 | 220 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 3.5 | 16 | 270 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 3.5 | 18 | 350 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 3.5 | 20 | 430 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 3.5 | 22 | 510 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 3.5 | 23 | 620 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 3.5 | 25 | 730 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 3.5 | 28 | 910 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 3.5 | 30 | 1075 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 3.5 | 33 | 1390 | 63.42 | 0.074 |
35kV AL-X (BS EN 50397-1)
Conducteur | Épaisseur of Isolation | Environ. Dans l'ensemble Diamètre | Environ. Dans l'ensemble Poids | Min. Breaking Load | Max.D.C Conducteur Resistance(20℃) | ||
Cross Sectional Zone | Na. and Diameter of wires | Outside Diamètre | |||||
mm2 | mm | mm | mm | mm | kg/km | kN | Ω/ km |
25 | 7/2.13 | 6.39 | 5.5 | 18 | 272 | 4.5 | 1.1489 |
35 | 7/2.51 | 7.53 | 5.5 | 19 | 317 | 5.913 | 0.8347 |
50 | 7/3.00 | 9 | 5.5 | 21 | 382 | 8.198 | 0.5748 |
70 | 7/3.55 | 10.65 | 5.5 | 22 | 463 | 11.288 | 0.4131 |
95 | 7/4.10 | 12.3 | 5.5 | 24 | 554 | 14.784 | 0.3114 |
120 | 19/2.80 | 14 | 5.5 | 26 | 651 | 19.89 | 0.2459 |
150 | 19/3.15 | 15.75 | 5.5 | 27 | 765 | 24.42 | 0.1944 |
185 | 19/3.50 | 17.5 | 5.5 | 29 | 889 | 29.832 | 0.1574 |
240 | 19/4.00 | 20 | 5.5 | 32 | 1084 | 38.192 | 0.1205 |
300 | 37/3.15 | 22.05 | 5.5 | 34 | 1258 | 47.569 | 0.1 |
400 | 37/3.66 | 25.62 | 5.5 | 37 | 1595 | 63.42 | 0.074 |
22kV and 35kV AAC ACSR XLPE Overhead Cable for Myanmar
22kV 35kV AAC ACSR XLPE
Power grids: To transmit electrical power from power generation plants to substations and then to distribution networks, cable could be used in underground or overhead installations.
Industrial applications: In factories, mines, and other industrial settings, the cable could be used to connect electrical equipment, motors, transformateurs, and other components within the facility’s power distribution system.
Infrastructure projects: For large-scale infrastructure projects such as airports, tunnels, des ponts, and road networks, cable can be specified for its durability, waterproofing, et résistance aux facteurs environnementaux.
Renewable energy systems: In wind farms, solar farms, and other renewable energy generation facilities, the cable could be used to connect turbines, panels, and other power generating units to the main power grid.
Utility networks: Utilities, including water, gas, and electric utilities, often use specialized cables in their networks. The cable could be tailored to specific requirements within these networks, such as increased fire resistance, low smoke emission, or resistance to chemicals and other environmental hazards.
Installations marines et offshore: Due to its potential impermeability and resistance to saltwater corrosion, the cable could be suitable for use in marine and offshore environments, such as connecting offshore wind turbines, câbles sous-marins, or subsea power distribution systems.
It is important to note that the exact specifications and capacities of the cable will depend on the manufacturer and the specific application requirements. Always consult the manufacturer’s technical documentation and specifications before selecting and using the cable.