STACIR-Invar Konduktor Paduan Termal Super Diperkuat
STACIR
STACIR Super Thermal Alloy Conductor Invar Reinforced conductors are ideal for re-conductoring projects, allowing existing transmission lines to increase capacity by simply replacing the current conductor. This upgrade enables them to carry twice the current of ACSR conductors of the same size, maintaining maximum sag and working tension without necessitating any tower modifications or reinforcements.
Core Wire (INVAR) : Aluminum-clad INVAR Wire/High Tensile Strength Aluminum-clad INVAR Wire
Konduktor (STAL) : Super Thermal Resistant Aluminum Alloy Wire used for continuous allowable temperature up to 210°C
We are STACIR, INVAR, STAL manufacturer and factory, we sale low price with good quality.
Data Sheet STACIR
PROPERTIES | STACIR (ACSR MOOSE EQUIVALENT) | STACIR ( ACSR ZEBRA EQUIVALENT) | STACIR (ACSR PANTHER EQUIVALENT) | |||
Typical factors | 3.53 mm | 0.1390 di dalam | 3.18 mm | 0.1252 di dalam | 3.00 mm | 0.1181 di dalam |
Reference specifications | IEC 62004 | IEC 62004 | IEC 62004 | |||
Total cross section area | 597.00 mm2 | 0.9254 in2 | 484.50 mm2 | 0.751 in2 | 261.50 mm2 | 0.4054 in2 |
Conductive wire | Al Zr AT3 | Al Zr AT3 | Al Zr AT1 | |||
Core wire | Aluminium clad Invar | Aluminium clad Invar | Aluminium clad Invar | |||
Conductor diameter | 31.77mm | 1.2508 di dalam | 28.62 mm | 1.1268 di dalam | 21.00 mm | 0.8268 di dalam |
Weight | 1993 kg/km | 1339.2 lbs/mile | 1582 kg/km | 1063.1 lbs/mile | 939 kg/km | 631 lbs/mile |
Ultimate tensile strength | 14641 kg | 32277.84 lbs | 11968 kg | 26384.89 lbs | 8436 kg | 18598.17 lbs |
DC resistance at 20°C temperature | 0.06 Ω/km | 0.09 Ω/mile | 0.07 Ω/km | 0.11 Ω/mile | 0.13 Ω/km | 0.21 Ω/mile |
Maximum operating temperature | 210°C | 410°F | 210°C | 410°F | 210°C | 410°F |
Current carrying capacity at maximum operating temperature | 1871 Amp | 1626 Amp | 1040 Amp |
STACIR/AW
STACIR/AW
Ukuran | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20HaiC | Modulus of Elasticity | Coefficient of Linear Expansion | Ultimate Tensile Strength | Current Carrying Capacity | ||
STAL | AL-INVAR | STAL | AL-INVAR | ||||||||
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Oh/km | Kgf/ mm2 | x10-6/HaiC | Kgf | A |
160 | 159.30 | 37.16 | 30 X 2.60 | 7 X 2.60 | 18.20 | 441.7 | 0.1745 | 6,140 | 16.0 | 6,140 | 909 |
240 | 241.30 | 56.29 | 30 X 3.20 | 7 X 3.20 | 22.40 | 669.1 | 0.1159 | 9,170 | 16.0 | 9,170 | 1,203 |
330 | 326.80 | 52.84 | 26 X 4.00 | 7 X 3.10 | 25.30 | 905.1 | 0.0869 | 10,000 | 17.5 | 10,000 | 1,452 |
410 | 413.40 | 67.35 | 26 X 4.50 | 7 X 3.50 | 28.50 | 1,145.5 | 0.0686 | 12,720 | 17.5 | 12,720 | 1,708 |
480 (Rail) | 483.84 | 33.54 | 45 X 3.70 | 7 X 2.47 | 29.61 | 1,340.7 | 0.0600 | 10,500 | 20.0 | 10,500 | 1,812 |
480(Cardinal) | 484.52 | 62.81 | 54 X 3.38 | 7 X 3.38 | 30.42 | 1,343.5 | 0.0591 | 13,280 | 18.3 | 13,280 | 1,846 |
Hi-STACIR/AW
Hi-STACIR/AW
Ukuran | Section Area | Conductor Construction | Approx. Overall diameter | Approx. Overall weight | Maximum DC resistance at 20HaiC | Modulus of Elasticity | Coefficient of Linear Expansion | Ultimate Tensile Strength | Current Carrying Capacity | ||
STAL | Hi-AL-INVAR | STAL | Hi-AL-INVAR | ||||||||
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | kg/km | Oh/km | Kgf/ mm2 | x10-6/HaiC | Kgf | A |
160 | 159.30 | 37.16 | 30/2.60 | 7/2.60 | 18.20 | 706.9 | 0.1745 | 8,040 | 16.0 | 6,500 | 909 |
240 | 241.30 | 56.29 | 30/3.20 | 7/3.20 | 22.40 | 1070.8 | 0.1159 | 8,040 | 16.0 | 9,700 | 1,203 |
330 | 326.80 | 52.84 | 26/4.00 | 7/3.10 | 25.30 | 1282.1 | 0.0869 | 7,580 | 17.5 | 10,500 | 1,452 |
410 | 413.40 | 67.35 | 26/4.50 | 7/3.50 | 28.50 | 1626.1 | 0.0686 | 7,590 | 17.5 | 13,300 | 1,708 |
480 (Rail) | 483.84 | 33.54 | 45/3.70 | 7/2.47 | 29.61 | 1580.0 | 0.0600 | 6,900 | 20.0 | 11,000 | 1,812 |
480(Cardinal) | 484.52 | 62.81 | 54/3.38 | 7/3.38 | 30.42 | 1795.7 | 0.0591 | 7,470 | 18.3 | 13,800 | 1,846 |